Goodrive10 Series Mini VFD Installation guidelines
-12-
RH≤90%
No condensation is allowed. The maximum relative humility should
be equal to or less than 60% in corrosive air.
-40°C–+70°C, and the temperature changing rate is less than
1°C/minute.
Running
environment
condition
The installation site should meet the following requirements.
Keep away from the electromagnetic radiation source;
Keep away from oil mist, corrosive gases and combustible gases;
Ensure foreign object like metal powder, dust, oil and water will not
fall into the VFD (do not install the VFD onto combustible object like
wood);
Keep away from radioactive substance and combustible objects;
Keep away from harmful gases and liquids;
Low salt content;
No direct sunlight.
When the altitude exceeds 1000m, derate by 1% for every increase
of 100m.
When the altitude exceeds 3000m, consult the local INVT dealer or
office for details.
Max. vibration acceleration: 5.8m/s
2
(0.6g)
The VFD should be installed on an upright position to ensure sufficient
cooling effect.
Note:
Goodrive10 series VFDs should be installed in a clean and ventilated environment
according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The VFD may be installed on the wall or in a cabinet.
The VFD must be installed in an upright position. Check the installation site according to the
requirements below. See Appendix B "Dimension drawings" for details.