Goodrive10 Series Mini VFD Function parameters
-68-
Function
code
Name
Description
Default
Modify
Termin
al 2
OFF
OFF
ON
ON
OF
F
OF
F
ON
ON
Termin
al 3
OFF
OFF
OFF
OF
F
ON
ON
ON
ON
Termin
al 4
ON
ON
ON
ON
ON
ON
ON
ON
step
8
9
10
11
12
13
14
15
Setting range of P10.(2n,1<n<17):
-100.0100.0%
P11 group Protection parameters
Function
code
Name
Description
Default
Modify
P11.01
Frequency
drop at
transient
power-off
0: Disable
1: Enable
0
P11.02
Frequency
drop ratio
at transient
power-off
Setting range: 0.00Hz/sP00.03 (max. output
frequency)
After the grid powers off, the bus voltage drops
to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make
the motor generate power again. The returning
power can maintain the bus voltage to ensure a
rated running of the VFD until the VFD is
powered on again.
Voltage class
220V
380V
Frequency drop
point at transient
power-off
260V
460V
Note:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
10.00Hz/
s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive10 Series and is the answer not in the manual?

INVT Goodrive10 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive10 Series
CategoryInverter
LanguageEnglish

Related product manuals