Goodrive10 Series Mini VFD Function parameters
-31-
Function
code
Name
Description
Default
Modify
P00.18
Function
restore
parameter
0:No operation
1:Restore the default value
2:Clear fault records
Note:
The function code will restore to 0 after
finishing the operation of the selected
function code.
Restoring to the default value will cancel
the user password, please use this function
with caution.
0
P01 group Start and stop control
Function
code
Name
Description
Default
Modify
P01.00
Start
mode
0: Start-up directly:start from the starting
frequency P01.01
1:Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
0
P01.01
Starting
frequency
of direct
start
Starting frequency of direct start-up means the
original frequency during the VFD starting. See
P01.02 for detailed information.
Setting range: 0.0050.00Hz
0.50Hz
P01.02
Starting
frequency
hold time
Set a proper starting frequency to increase the
torque of the VFD during starting. During the
retention time of the starting frequency, the
output frequency of the VFD is the starting
frequency. And then, the VFD will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the VFD will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
0.0s