Function and Features
 
  Copyright © ITECH Electronic Co., Ltd.  32 
10.0000V  0.0000A 
0.00W  0 TRAN 
11.  Press [On/Off] key to open input and press [Trig] key (Triggering key) 
The load will switch after receipt of every trigger signal. The load will 
continuously switch between A and B value. Time of operations is shown at 
bottom right. 
12.  Press CC/CV/CR/CW key or any composite function key to exit dynamic 
test function. Repeat Steps 1-11 to continue parameter setting and 
operation of dynamic test. 
3.9.3 Toggle mode 
Under toggle mode, after enabling dynamic test operation, the load will be 
switched continuously between A value and B value after receipt of every 
trigger signal. 
 
 
Taking CC mode as example (operations under other modes are similar), when 
output voltage and current of the tested instrument are 10V and 3A respectively, 
the load current will switch from 1A and 2A. Set the dynamic test parameters 
and perform the test as follows: 
1.  Press [Tran] key. Operate Left/Right key. Move to On and press [Enter] for 
confirmation. 
TRANSITION 
On    Off 
2.  Select Toggle, Press [Enter] key (The Trig lamp that indicates VFD screen 
status is on). 
TRANSITION 
Continuous  Pulse  Toggle 
3.  Operate Left/Right key and select high rate and low rate. Move to the 
High-Rate and press [Enter] key. 
TRANSITION 
High-Rate  Low-Rate 
4.  Set ascending slope and press [Enter] key. 
TRANSITION 
Rise up=2.000A/uS 
5.  Set descending slope and press [Enter] key for confirmation. 
10A
5A
TRG
TRG
Toggled Transient Operation