Function and Features
 
  Copyright © ITECH Electronic Co., Ltd.  39 
keys to set final voltage value and press [Enter] key. 
4.  Press [Esc] to exit setting. 
Start timer function 
5.  Press [Shift] + 5 keys to enter system menu. Press Right key till “Displ” 
flicks and press [Enter] key. 
6.  Press Left/Right Key to select “On”. Start timer function and press [Enter] 
key. 
7.  Press [Esc] to exit setting. 
8.  VFD second line will display time 0.0000S between power value and set 
value. 
OFF    CC 
0.0001V 0.0002A 
0.00W 0.0000S CC=0.000A 
 
Measurement of rise time 
9.  Connect DC power to be tested to the input terminal of the electronic load. 
The power is set with a value that is higher than the set final voltage value. 
Keep power output in OFF status. 
10.  Set a constant current value on the load and open the load input. 
11.  Open power output. 
12.  The electronic load timer starts timing. After ending, time will keep stable, 
which is rise time of voltage. 
13.  Close the power output. The electronic load VFD will display voltage drop 
time. 
3.15 Configuration save function 
The electronic load can save some commonly-used parameters in 100-group 
(0-99) NVM for convenient and fast usage. Saving parameters comprise 
working mode, voltage, current, etc. The Save key can be used for saving 
parameters. The RECALL key is for quick invoking. 
Operation steps 
If the operator needs to save configured parameter values for direct recall in 
follow-up operation, refer to the steps below: 
e.g., power supply 6V and 3A. The electronic load works under constant current 
(CC) 1A. Save "CC 1A" in register 9 for recall. 
  SAVE 
1.  Set parameters and press [Shift] + 4 (Save) to save data. Press 9 key (to 
select in which group the data is to be saved). 
5.8949V    0.99994A 
5.89W    SAVE 9
 
2.  Press [Enter] key for confirmation. 
5.8949V    0.99994A 
5.89W    cc=1.000A