Technical Data
Section 5
Hydrovar Power Supply
Rated Output Voltage Limits 48-62 HZ
Rated Input Recommended Maximum
Current Line Protection Wire Size
Cat #* HP V Amps Amps AWG
HVM1202 2
1 Ph, 220-240V -10%,
14 20 14
HVM1203 3
+15%
20 25 10
HVM3403 3 7.6 10 14
HVM3405 5
3 Ph, 380-460V
11.4 15 14
HVM3407 7.5
+-15%
15.1 20 12
HVM3410 10 19.6 20 10
HVM3415 15 27.8 30 8
* Listed catalog numbers are for master drives. Details also apply to corresponding basic and single units.
Hydrovar Output to the Motor
Rated Output Voltage Limits 48-62 HZ
Rated Current
Motor Connection Wires
Output
Cat #* HP V A AWG
HVM1202 2
3 Ph, 240V
7 14
HVM1203 3 10 14
HVM3403 3 5.7 14
HVM3405 5 9 14
HVM3407 7.5 3 Ph, 480V 13.5 14
HVM3410 10 17 12
HVM3415 15 23 10