EasyManuals Logo

ITT Hydrovar User Manual

ITT Hydrovar
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26
Electrical Installation and Wiring
Connection Example
External switch to enable the
SOLO RUN (Hand Mode)
Example:
Low water or other
emergency off switch
Thermistor
(mounted in the motor terminal box)
Recommended connections of external protective devices:
Basic drive Thermistor X1/PTC
Emergency switch X1/PTC As described above
Low water switch X1/PTC
Master drive Thermistor X1/PTC As described above
External release X3/7-8
On the control card
Low water switch X3/11-12
When the HYDROVAR is used as a Basic drive in a multi-pump system, the X2 terminals
on the power unit are used for the serial RS-485 connection to the other HYDROVAR
units in the system. (Note: Internal interface is not available on Single Inverters!)
X2 RS485-Interface – Power Unit
X2/ SIO - Internal SIO-interface: SIO-
Internal interface
SIO+ Internal SIO-interface: SIO+
for multi-pump-systems
GND GND, electronic ground
……. Terminals not available for HYDROVAR Single drives
The internal RS-485 Interface on the power unit is used for the communication be-
tween up to 8 HYDROVARs in a multi-pump system (minimum 1 Master drive). Use the
same terminals to continue on to the next HYDROVAR if required. Terminals X4/4-6 can
also be used for RS-485 communication on all Master drives.
X2
GND
SIO + RS485 – internal interface
SIO -
X1
SL
SL
PTC
PTC
SW 1
Auto
Manual
S
S
}

Other manuals for ITT Hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ITT Hydrovar and is the answer not in the manual?

ITT Hydrovar Specifications

General IconGeneral
BrandITT
ModelHydrovar
CategoryInverter
LanguageEnglish

Related product manuals