Page 5-6 LCD Programming
Revised 10/14
ITW Dynatec
D SERIES V6 DCL ASU Manuals
Setup Your System's Parameters
System Parameter Setup refers to the process of programming the controller to meet the specif
ic temperature requirements of your production. Temperature setpoints for each temperature
zone must be programmed as well as a standby temperature and high/ low alarm tolerances.
Choices must be made for program selection and pump (or motor) conditions. If desired, tem
perature zone offsets and/ or a temperature zone enable may be selected.
The following is a stepbystep procedure for setting up the DynaControl with your system's
parameters.
Temperature Zones
Selecting Temperature Zones
From the Overview Screen, turn the Input Wheel slowly to view each temperature zone. As the
wheel is turned, you will see the names of the individual temperature zones on the top line of
thedisplay.Zonenamesmaybereprogrammed to suit the user, but ITW Dynatec's typical D
Series zone names are: PREMELT (dropin grid), HOPPER, HOSE, HEAD and AUX.
To select a zone, simply stop turning the wheel when the desi red zone's name appears (example
below: HEAD 2). To the right, displayed on the top line, is this zone's programmed setpoint (ex.
SET: 320F) and the actual current temperature of the zone (ex. ACT: 319F).
Below the zone's name is the bargraph with the selected zone highlighted. Below the bargraph
you can see that this zone is #2 of the system's applicators. At the far right of the display, you
can see that this zone is turned ON.
Head 2 zone is selected Head 2's Setpoint Head 2's Actual (current) Temperature
BarGraph
of all
zones
Head 2 is
turned ON (I)
Head 2 is highlighted on the bargraph