UMG 103-CBM www.janitza.com
54
General
Net weight (with attached plug-in connectors) approx. 200 g (0.44 lbs)
Device dimensions (W x H x D) 71.5 x 98 x 46 mm (2.82 x 3.86 x 1.18 in)
Environmental conditions during operation
The device:
• Is for weather-protected and stationary use.
• Fulfills the operating conditions according to DIN IEC 60721-3-3
• Has protection class II according to IEC 60536 (VDE 0106, part 1)
and does not require a ground wire connection.
Working temperature range -25°C .. +60°C (-13 °F ... 140°F)
Relative humidity 5% to 95% (at +25 °C / 77 °F), no condensation
Operating elevation 0 .. 2000 m (6562 ft) above sea level
Pollution degree 2
Housing flammability classification UL 94V-0
Mounting orientation As desired
Installation/assembly DIN rail, 35 mm, to IEC/EN60999-1, DIN EN50022
Ventilation No forced ventilation required.
Stress due to impact 2 joules, IK07 according to IEC/EN61010-1:2010
Protection against foreign matter and water IP 20 according to EN60529, September 2000, IEC60529:1989
Transport and storage
The following information applies to devices that are transported or stored in their original packaging.
Free fall 1m (39.37 in)
Temperature -20°C ... +70°C (68 °F ... 158 °F)
Relative humidity 0 to 90% RH
13. Technical data
13.1 Technical data
Measurement data recording
Memory (flash) 4 MB, (1024 sectors of 4 kB ea.)
Data set storage (all profiles enabled) approx. 16,000 records
Battery (soldered), typical life expectancy BR 1632, 3V,
8-10 years
Firmware
Firmware update Update via GridVis software.
Firmware download at www.janitza.de