Mode (delta)
If the difference of two neighbouring scanning
points exceeds the set limit value, a transient is
recognized.
Off - Transient monitoring is switched off.
Automatic - Factoring pre-setting. The limit
value is calculated automatically and is 0.2175
times the current 200ms effective value.
Manual - Transient monitoring uses the adjus-
table limit value under „Trns U“.
Mode (envelop)
If a scanning value exceeds the range of the enve-
lope, a transient is recognized.
Off - Transient monitoring is switched off.
Automatic - Factoring pre-setting. The enve-
lope is calculated automatically and is ± 5% of
nominal voltage.
Manual - Transient monitoring uses the adjus-
table envelop.
Apply AUX / MAIN
The transient monitoring is set for the main and
auxiliary measurement. You can apply the settings
from the auxiliary or main measurement.
No - The main and auxiliary measurement
settings are not transferred.
Yes - The settings of the auxiliary or main
measurement will be taken.

Other manuals for janitza UMG 511

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the janitza UMG 511 and is the answer not in the manual?

janitza UMG 511 Specifications

General IconGeneral
Brandjanitza
ModelUMG 511
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals