EasyManua.ls Logo

JCM Technologies KEEROLL - KEEroll Configuration and Startup; Power Supply Connection; Limit Switch Adjustment; Dipswitch Options Selection

JCM Technologies KEEROLL
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration / Starting up
Connect the power supply
Adjusting limit switch
Door MUST BE AT HALFWAY position before
starting the limit switch adjusting
Dipswitch 1 in ON. Door will move in dead man mode. Keep pressed or to move up
or down the door.
Press , to change the phase of the motor in case the door is not moving in the proper sense.
Dipswitch 1 in OFF to exit dead man mode.
Options selection
Dipswitch function OFF ON
1- DEADMAN Normal operation Dead man operation
2- AUTOCLOSE Do not close automatically Close automatically
3- PRE-FLASH Pre-flash disabled 3s pre-flash enabled
4- ALARM* (KEEalarm needed) Alarm function disabled Alarm function enabled
5- COURTESY LIGHT / ALARM Courtesy light output External alarm output
6- TEST PHOTO Test photocell disabled Test photocell enabled
* Optional alarm. JCM can provide you KEEalarm
jcmtechnologies
15

Table of Contents