SECTION 2 - OPTIVIEW OPERATION
used to provide energy savings following chiller start-
up and is adjustable from 30 to 100%, with 100% as
the default setting.
Pulldown Demand Time
Access Level Required: OPERATOR
This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts.
The pulldown demand time is adjustable from 0 to 255
minutes, with 0 minutes as the default.
Motor Cooling Pump
Access Level Required: Service
This enables motor cooling pump when one of the
motor winding temperatures exceed the setpoint pro-
grammed on the Motor Temperature Screen. The mo-
tor cooling pump can only operate when the machine
is running.
Change Setpoint
Access Level Required: VIEW
Allows user to enter login password to change motor
settings. This button is only present at the “View” ac-
cess level.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Motor Temperature
Access Level Required: VIEW
Advances the display to the Motor Temperature screen.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK OPTIVIEW CONTROL CENTER and is the answer not in the manual?

Johnson Controls YORK OPTIVIEW CONTROL CENTER Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK OPTIVIEW CONTROL CENTER
CategoryControl Panel
LanguageEnglish

Related product manuals