5-2
Contents
Cause
Action
The AC power supply is not input
within the specified voltage range.
Connect the AC supply within the
specified voltage range.
The display processing unit is
faulty.
Request repairs to the distributor.
The power is not
supplied to the
Touch Panel Display
unit.
The AC power supply is not
connected.
Check the following and start.
The main power is ON
UPS output is ON
The ship's power supply is supplied
The Touch Panel Display unit is
faulty.
Request repairs to the distributor.
Although the power
is supplied to the
Touch Panel Display
unit, the screen is not
displayed.
The display processing unit has
not been started.
Start the display processing unit.
The graphic board of the display
processing unit is broken.
Disconnect the DVI cable from the
4-branch cable and connect it to the
main unit.
Also, ask your dealer for repair.
The brightness of the Touch Panel
Display unit is set to the lowest
level.
Adjust the brightness of the Touch
Panel Display unit to the proper
brightness level.
The Touch Panel Display unit is
faulty.
Request repairs to the distributor.
The touch panel
does not respond.
The touch panel operation of the
Touch Panel Display unit is set to
Disable.
Set the touch panel operation of the
Touch Panel Display unit to Enable.
USB cable is disconnected.
Reconnect the USB cable of the touch
panel display unit and the processing
unit.
The Touch Panel Display unit is
faulty.
Request repairs to the distributor.
The key file which is
necessary to Cloud
communication is not
made
The gateway setting is not correct
Start the command prompt and check
the communication with the gateway.
If cannot confirm the communication,
contact network administrator.
Not set DNS in SAT LAN
Display SAT LAN properties. Confirm
that DNS is set up.
Ship network is not approved to
port 443
Start IE in Data Processing Unit.
Confirm that
“https://ssv.jmarinecloud.com” is
opened. If cannot opened, request
the network administrator for
permission of port: 443.
Although the Touch
The stylus pen is not activated.
Activate the stylus pen.