27
5 Configuration and parameter tables
Analog output
C114 Supply frequency/temperature compensation
X
0 50Hz / internal temperature compensation
150Hz / fixed temperature compensation
260Hz / internal temperature compensation
360Hz / fixed temperature compensation
Para-
meter
Explanation Value range factory
setting
X
C115 value with fixed
temperature
compensation
0—100°C
0
C116 Measurement display
X
0 percent
1as output signal (mA or V)
2in configurable unit
(see parameter C002 page 23)
C211 Function of the analog output
X
0 0—20mA
1420mA
2010V
3210V
The limits can be inverted by swapping the two parameters
SCL and SCH.
C212 Signal of output on
probe break/short-circuit
X
0 positive (22mA or 11V - according to C211)
1negative (0mA or 0V - according to C211)