17Kamstrup A/S • 5512952_C6_GB_07.2015
MULTICAL® 602 & ULTRAFLOW®
8 Informtion codes ”INFO”
MULTICAL® 602 constntly monitors number of importnt functions. In cse of serious error in
mesuring system or instlltion, “INFO” is displyed nd n info-code cn be red by ctivting
the top front key until the mesuring unit sys “INFO”. The info code is only displyed when the
error is present.
Info code Description Response time
0 No irregulrities -
1 Supply voltge hs been interrupted -
8 Temperture sensor T1 outside mesuring rnge 1…10 min.
4 Temperture sensor T2 outside mesuring rnge 1…10 min.
32 Temperture sensor T3 outside mesuring rnge 1…10 min.
64 Lek in cold wter system 24 hours
256 Lek in heting system 24 hours
512 Burst in heting system 120 s.
ULTRAFLOW® info (ctive when CCC=4XX)
16 Flow sensor V1, communiction error After one dy (t 00:00)
1024 Flow sensor V2, communiction error After one dy (t 00:00)
2048 Flow sensor V1, wrong pulse figure After one dy (t 00:00)
128 Flow sensor V2, wrong pulse figure After one dy (t 00:00)
4096 Flow sensor V1, signl too wek (ir) After one dy (t 00:00)
8192 Flow sensor V2, signl too wek (ir) After one dy (t 00:00)
16384 Flow sensor V1, wrong flow direction After one dy (t 00:00)
32768 Flow sensor V2, wrong flow direction After one dy (t 00:00)
If number of info codes pper t time, the sum of info codes is displyed. If e.g. both
temperture sensors re outside mesuring rnge, info code 12 is displyed.