2
1
KEB COMBIVERT F4-C
8
Name: Basis
09.04.99
© KEB Antriebstechnik, 1999
All Rights reserved
Product DescriptionSummary
Chapter Section
Page Date
Unit Sizes 400V-Class (18-29)
1) From housing size M fuses of Type Ferra Z 6,6 URD xxx must be used.
2) This data is only valid for units with internal brake transistor (see „2.1.4 Type Code“).
3) At mains voltage ≥460V multiply the nominal current with factor 0,86.
4) These units can be used with one or more braking modules. For more informations cantact KEB.
Inverter Size 18 19 20 21 22 23 28 29
Output nominal power [kVA] 35 42 52 62 80 104 256 319
Max. motor rating [kW] 22 30 37 45 55 75 200 250
Output nominal current [A] 50 60 75 90 115 150 370 460
Max. short-time current [A] 75 90 112,5 135 172,5 225 462,5 575
OC-tripping current [A] 90 108 135 162 207 270 555 690
Nominal input current [A] 55 66 83 100 127 165 410 510
Housing size HRHRR RLRLRLMUMUUNUNUPU P P
Rated operating frequency [kHz] 8 16 4 8 8 4/8 8 4 8 2 4 8 8 8 4 8 4 4 4 4 2 2 2 1
Max.operating frequency [kHz] 16 16 16 16 16 16 16 4 16 2 16 8 16 8 4 8 4 4 4 4 2 2 2 1
Power loss at nominal operating [W] 610 850 540 750 900 1100 1100 1200 1400 1300 1400 1800 1900 2200 200 2400 2300 2300 2700 2800 2900 3100 3500 4200
Stall current at 8kHz [A] 45 50 - 60 75 90 90 - 115 - - 140 150 - - 180 - - - - - - - -
Stall current at 16kHz [A] 20 40 - 27 33,7 40,5 - - 51,7 - - - - - - - - - - - - - - -
Max. heat sink temperatureT
OH
[°C] 90 79 90 90 90
Max. permissible mains fuse (inert)
1)
[A] 80 80 100 160 160 550
700
Line cross section [mm²] 25 25 35 50 50 185 2x120
Min. braking resistor
2)
[Ω]1391399 9896 6
4)
5
4)
4
4)
4
4)
4
4)
4
4)
Typ. braking resistor
2)
[Ω]22 16 13 11 9 6
4)
6
4)
6
4)
4
4)
4
4)
4
4)
Max. braking current [A] 63 88 63 88 88 88 100 88 133 133
4)
160
4)
200
4)
200
4)
200
4)
200
4)
Tightening torque for terminals [Nm] 2,5
Mains voltage
3)
[V]
305...500 +/-0 (400V Nominal voltage)
1)
Phases 3
Mains frequency [Hz] 50 / 60 +/- 2
Output voltage [V] 3 x 0...U Mains
Output frequency [Hz] see control board
Shielded motor line length [m] 100 100
Storage temperature [°C] -25...70 °C
Operating temperature [°C] -10...45 °C ...40°C ...35°C
Model / protective system IP20
Relative humidity max. 95% without condensation
Tested in accordance with... EN 61800-3
Climatic category 3K3 in accordance with EN 50178
400 450
95 95 95 120 150
200 315 315
24 25 26 27
125 145 173 208
90 110 132 160
180 210 250 300
225 262,5 312,5 375
275 330
270 315 375 450
198 231