KEB COMBIVERT F5-G / B
Name: Basis
6
Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section PageDate
Operating and Appliance Data
Adr.
min max
default
0211h
ru.17 Active current
0.1
A
-
+unit-dependent-unit-depend.
Display of the torque-forming active current (stator losses already deducted). Negative current corresponds to generatoric
operation, positive current corresponds to motoric operation. The more precise the motor data are entered, the more
precise is the indication of the active current. The maximum values depend on the size of the inverter.
Adr.
min max
default
Adr.
min max
default
0212h
ru.18 DC-link voltage
1
V
-
10000
Display of current DC-link voltage. Typical values are
Normal operation: 230V-class 300-330V over volt. (E.OP): approx. 400V under volt. (E.UP): approx. 216V
400V-class 530-620V approx. 800V approx. 240V
0213h
ru.19 DC-link voltage / peak value
1
V
-
10000
ru.19 permits the detection of short-time voltage rises within an operating cycle. The higest occurred value of ru.18 is
stored in ru.19. The peak value memory can be cleared by pressing the keys UP, DOWN or ENTER and by bus through
writing any chosen value to the address of ru.19. Switching off the inverter also results in a clearing of the memory.
Adr.
min max
default
0214h
ru.20 Output voltage
1
V
-
7780
Display of the current output voltage.