6 1
Name: Basis
KEB COMBIVERT F5-G / B
10
24.06.02
Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section Page Date
Operating and Appliance Data
Adr.
min max
default
0216h
ru.22 Internal input state
1
-
-
40950
Display of the digital external and internal inputs set currently. The input is only regarded as set if it is available as
effective signal to the further processing (i.e. accepted through Strobe, edge-triggering or logic operation). According to
following table a specific decimal value is given out for each digital input. If several inputs are controlled, the sum of the
decimal values (see ru.21) is indicated (also see Chapt. 6.3 „Digital inputs“)
Adr.
min max
default
0215h
ru.21 Input terminal state
1
-
-
40950
Display of the digital inputs controlled currently. The logic levels are indicated at the input terminals or at the internal
inputs regardless of the following logic operations (also see Chapt. 6.3 „Digital inputs“). According to following table a
specific decimal value is given out for each digital input. If several inputs are controlled, the sum of the decimal values
is indicated.
Bit -No. Decimal Value Input Terminal
0 1 ST (prog. input „control release/Reset“) X2A.16
1 2 RST (prog. input „Reset“) X2A.17
2 4 F (prog. input „forward“) X2A.14
3 8 R (prog. input „reverse“) X2A.15
4 16 I1 (prog. input 1) X2A.10
5 32 I2 (prog. input 2) X2A.11
6 64 I3 (prog. input 3) X2A.12
7 128 I4 (prog. input 4) X2A.13
8 256 IA (internal input A) none
9 512 IB (internal input B) none
10 1024 IC (internal input C) none
11 2048 ID (internal input D) none