KEB COMBIVERT F5-G / B
Name: Basis
6
Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section PageDate
Operating and Appliance Data
Adr.
min max
default
0217h
ru.23 Output condition state
1
-
-
2550
With parameters do.0...do.7 switching conditions can be selected, that serve as a base for setting the outputs. This
parameter indicates which of the selected switching conditions are met before they are linked or inverted by programmable
logic (also see Chapt. 6.3 „Digital outputs“). According to following table a specific decimal value is given out for the
switching conditions. If several of the selected switching conditions are met, the sum of the decimal values is indicated.
Bit -No. Decimal value Output
0 1 switching condition 0 (do.0)
1 2 switching condition 1 (do.1)
2 4 switching condition 2 (do.2)
3 8 switching condition 3 (do.3)
4 16 switching condition 4 (do.4)
5 32 switching condition 5 (do.5)
6 64 switching condition 6 (do.6)
7 128 switching condition 7 (do.7)
Adr.
min max
default
0217h
ru.24 State of output flags
1
-
-
2550
Display of the links after logic step 1. The selected switching conditions are linked in logic step 1 (do.8...24) and
indicated here (see Chapt. 6.3 „Digital outputs“). According to following table a specific decimal value is given out for
each linkage. If several links are set, the sum of the decimal values is indicated.
Bit -No. Decimal value Output
0 1 flag 0
1 2 flag 1
2 4 flag 2
3 8 flag 3
4 16 flag 4
5 32 flag 5
6 64 flag 6
7 128 flag 7