Name: Basis
KEB COMBIVERT F5-G / B
12
24.06.02
Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section Page Date
Operating and Appliance Data
Adr.
min max
default
021Ah
ru.26 Active parameter set
1
-
-
70
The frequency inverter F5-GENERALand F5-BASIC can fall back on 8 internal parameter sets (0-7). Through programming
the inverter can change parameter sets autonomously and can thus start different modes of operation. This parameter
shows the parameter set, with which the inverter is operating currently. Independent of it another parameter set can be
edited by bus (also see chapter 6.8 „Parameter sets“).
Adr.
min max
default
021Bh
ru.27 Analog input 1 / display before amplification
0.1
%
-
100-100
This parameter indicates the value of the analog signal AN1 on the differential voltage input (terminal X2A.1 / X2A.2)
before signal amplification in percent. In dependence on An.0 the indicated value 0...±100 % corresponds to: 0...±10 V;
0...±20 mA or 4...20 mA (also see Chapt. 6.2 „Analog inputs“).
Adr.
min max
default
021Ch
ru.28 Analog input 1 / display after amplification
0.1
%
-
400-400
This parameter shows the value of the analog signal AN1 in percent after passing the characteristic amplifier. The range
of indication is limited to ±400 % (also see Chapt. 6.2 „Analog inputs“).
Adr.
min max
default
0218h
ru.25 Output terminal state
1
-
-
2550
Display of the external and internal digital output set currently. According to following table a specific decimal value is
given out for each digital output. If several outputs are set, the sum of the decimal values is indicated.
Bit -No. Decimal value Output Terminal
0 1 O1 (transistor output 1) X2A.18
1 2 O2 (transistor output 2) X2A.19
2 4 R1 (relay RLA,RLB,RLC) X2A.24...26
3 8 R2 (relay FLA,FLB,FLC) X2A.27...29
4 16 OA (internal output A) none
5 32 OB (internal output B) none
6 64 OC (internal output C) none
7 128 OD (internal output D) none