CP - ParameterOperation
4
3
KEB COMBIVERT F5-M / S20
Name: Basis
17.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2003
All Rights reserved
Relay output 1 / Function
Relay output 2 / Function
CP.33 and CP.34 determine the function of the two outputs.
(terminal X2A.24...X2A.26 and X2A.27...X2A.29)
1)
Switching level of CP.33 = 100; Switching level of CP.34 = 4
Value Function
0 No function (generelly off)
1 Generelly on
2 Run signal; also by DC-braking
3 Ready signal (no error)
4 Fault relay
5 Fault relay (not at under voltage error)
6 Warning or error message at abnormal stopping
7 Overload alert signal
8 Overtemperature alert signal power modules
9 External Overtemperature alert signal motor
10 Only application-mode
11 Overtemperature alert signal interior OHI
12-19 Only application-mode
20 Actual value = set value (CP.3 = Fcon, rcon; not at noP, LS error, SSF)
21 Accelerate (CP.3 = FAcc, rAcc, LAS)
22 Decelerate (CP.3 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
24 Utilization > switching level
1)
25 Active current > switching level
1)
26 Only application-mode
27 Real value (CP.1) > switching level
1)
28 Set value (CP.2) > switching level
1)
29-30 Only application-mode
31 Absolut set value on AN1 > switching level
1)
32 Absolut set value on AN2 > switching level
1)
33 Only application-mode
34 Set value on AN1 > switching level
1)
35 Set value on AN2 > switching level
1)
36-39 Only application-mode
40 Hardware current limit activated
41 Modulation on-signal
42-46 Only application-mode
47 Ramp output value > switching level
1)
48 Apparent current (CP.4) > switching level
1)
49 Forward running (not at nOP, LS, abnormal stopping or error)
50 Reverse running (not at nOP, LS, abnormal stopping or error)
51 Warning E.OL2
52 Current regulator limit reached
53 Speed regulator limit reached
54-62 Only application-mode
63 Absolut value ANOUT1 > switching level
1)
64 Absolut value ANOUT2 > switching level
1)
65 ANOUT1 > switching level
1)
66 ANOUT2 > switching level
1)
67-69 Only application-mode
70 Driver voltage active (safety-relay)
71-72 Only application-mode
73
74
75 Only application-mode