Functional Description Protective Functions
Param. Adr.
min
max
default
ENTER
PROG.
R/W
Step
Used Parameters
fr. 8 0908h ✔✔- 0 7 1 0 not at F5-S
Pn.12 040Ch -- 0 7 1 7 -
Pn.13 040Dh - - 0 120 s 1 s 0 s -
Pn.14 040Eh -- 0 6 1 6 -
Pn.15 040Fh - - 0 % 100 % 1 % 100 % only at F5-S
dr.11 060Bh ✔✔- 0 1 1 1 not at F5-S
dr.12 060Ch ✔✔- 0,0 710,0A 0,1A LTK not at F5-S
dr.34 0622 - - 0,1 s 10,0 s 0,1 s 0,5 s only at F5-S
dr.35 0623 - - 0,1 s 10,0 s 0,1 s 0,2 s only at F5-S
dr.36 0624 - - 0,1 s 10,0 s 0,1 s 5,0 s only at F5-S
ru.15 020Fh - - - 0,0 A 6553,5 A 0,1 A - -
The KEB COMBIVERT provides another possibilitiy to protect the motor by connecting
an external temperature monitoring. Following components can be connected to
terminals T1/T2:
External error control
procedure
Thermo contact
(NC contact)
Temperature sensor (PTC)
1650...4k tripping resistance
750...1650 reset resistance
T1
T2
T1
T2
With these two parameters the behaviour of the terminals T1/T2 is determined. The
function is described in Chapter 6.7.6.
dOH stopping mode (Pn.12)
dOH delay time (Pn.13)