9 1
KEB COMBIVERT F5
8
Name: Basis
04.05.04
Error Assistance
Chapter Section Page Date
© KEB Antriebstechnik, 2002
All Rights reserved
A.buS ABN.STOP bus 93 Warning: Watchdog for communication between operator/
control card or operator/PC has responded. The response to
this warning can be programmed (see chapter 6.7 “Response
to errors and warning messages”).
A.dOH ABN.STOP drive over heat 96 The motor temperature has exceeded an adjustable warning
level. The switch off time is started. The response to this
warning can be programmed (see chapter 6.7 “Response to
errors or warning messages”). This warning can be generated
only with a special power circuit.
A. EF ABN.STOP external fault 90 This warning is triggered via an external input. The response
to this warning can be programmed (see chapter 6.7
“Response to errors or warning messages”).
A.ndOH no A. drive overheat 91 The motor temperature is again below the adjusted warning
level. The switch off time is stopped.
A.nOH no A. overheat pow.mod. 88 The heat sink temperature is again below the adjusted
warning level.
A.nOHI no A.STOP overheat int. 92 The temperature in the interior of the inverter is again below
the warning threshold.
A.nOL no ABN.STOP overload 98 Warning: no more overload, OL counter has reached 0 %.
A.nOL2 no ABN.STOP overload 2 101 The cooling time after “Warning! Overload during standstill”
has elapsed. The warning message can be reset.
A. OH A.STOP overheat pow.mod 89 A level can be defined, when it is exceeded this warning is
output. A response to this warning can be programmed (see
chapter 6.7 “Response to errors or warning messages”).
A.OH2 ABN.STOP motor protect. 97 Warning: electronic motor protective relay has tripped. The
response to this warning can be programmed (see chapter
6.7 “Response to error or warning messages”).
A.OHI ABN.STOP overheat int. 87 The temperature in the interior of the inverter lies above the
permissible level. The switch off time was started. The
programmed response to this warning message is executed
(see chapter 6.7 “Response to errors or warning messages”).
A. OL ABN.STOP overload 99 A level between 0 and 100 % of the load counter can be
adjusted, when it is exceeded this warning is output. The
response to this warning can be programmed (see chapter
6.7 “Response to errors or warning messages”).
A.OL2 ABN.STOP overload 2 100 The warning is output when the standstill continuous current
is exceeded (see technical data and overload
characteristics). The response to this warning can be
programmed (see chapter 6.7 “Response to errors and
warning messages”). The warning message can only be reset
after the cooling time has elapsed and A.nOL2 is displayed.
A.PrF ABN.STOP prot. rot. for. 94 The drive is driven onto the right limit switch. The response
to this warning can be programmed (see chapter 6.7
“Response to errors and warning messages”).
A.Prr ABN.STOP prot. rot. rev. 95 The drive is driven onto the left limit switch. The response to
this warning can be programmed (see chapter 6.7 “Response
to errors and warning messages”).
Display COMBIVIS Value Meaning

Table of Contents

Other manuals for KEB COMBIVERT F5 Servo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Servo and is the answer not in the manual?

KEB COMBIVERT F5 Servo Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Servo
CategoryDC Drives
LanguageEnglish

Related product manuals