1502756-02 - 184 -
Checking the belt drive
for tension and
alignment
Initially after 10
ventilator start-ups,
then every 1600
hours/after 12 months at
the latest
Only if belt drive
available
Changing the V-belt
Every 1600 hours/after
12 months at the latest
Only if belt drive
available
Lubricating the fan
bearings
Initially after brief start-
up phase, then every
1600 hours/after 12
months at the latest
Only if lubricating
nipple fitted
Replacing the main
filter cartridge
As required
See the control display
for current status, filter
replacement at
2300 Pa, switch-off at
2800 Pa
Filter mat replacement
Extraction capacity
regulation
Once per month
Only if extraction
capacity regulation
present
Filter replacement
Safety filter Dust
collection container
Every 1600 hours/after
12 months at the latest
or if damaged/if
disposal bag is missing
Tab. 81: Maintenance schedule