6. Alarm / relay settings
F400
Page 17
1
> F 100
Step
Go into configuration mode (see page 2). The folder number displayed
corresponds to the last configuration folder used.
2
> F 400
Step
Select the folder “400” and validate with .
02
3
F 406
Step
>
4
Step
With and keys, set the required time-delay: from 00 to 60 seconds.
If you do not need the time-delay, enter 00.
Validate with .
15
F 406
>
15
5
F 406
Step
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
with and keys , you can choose another sub-folder from the folder 400.
>
Alarm 1 Alarm 2 Relay 1 Relay 2
Tempo “406” “411” “416” “421"
Select sub-folder
and validate with .
6.g.2 - Time-delay
Class 200 transmitter configuration via keypad