EasyManuals Logo

KitchenAid KEMS308S User Manual

KitchenAid KEMS308S
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
2-3
Models rated from 7.3 to 9.6 kW at 240 volts
(5.5 to 7.2 kW at 208 volts) require a separate
40-amp circuit. Models rated at 7.2 kW and
below at 240 volts (5.4 kW and below at 208
volts) require a separate 30-amp circuit.
A time-delay fuse or circuit breaker is recom-
m
ended.
Connect directly to the fused disconnect (or
circuit breaker box) through flexible, armored
or nonmetallic sheathed, copper cable (with
grounding wire). See “Make Electrical Con-
n
ection,” page 2-5.
Flexible cable from the oven should be con-
n
ected directly to the junction box.
Fuse both sides of the line.
D
o not cut the conduit. The length of conduit
provided is for serviceability of the oven.
A UL listed or CSA approved conduit con-
nector must be provided.
If the house has aluminum wiring follow the
procedure below:
1. Connect a section of solid copper wire to
the pigtail leads.
2. Connect the aluminum wiring to the added
section of copper wire using special con-
n
ectors and/or tools designed and UL
listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s
recommended procedure. Aluminum/copper
connection must conform with local codes
and industry accepted wiring practices.

Table of Contents

Other manuals for KitchenAid KEMS308S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KitchenAid KEMS308S and is the answer not in the manual?

KitchenAid KEMS308S Specifications

General IconGeneral
BrandKitchenAid
ModelKEMS308S
CategoryMicrowave Oven
LanguageEnglish

Related product manuals