To set up the router for a service connection, do the following:
1 Set up the computer and router for a single cable connection as described in the topic
Single-cable connection on page 11.
2 Connect the MS/TP to NetSensor cable between the router and the bottom of a
NetSensor or STE-6000 sensor with a network port.
3 Assign a unique device instance number and network number to the service tool
program.
4 Log in to the router with an HTML5 browser.
5 Assign a unique device instance number to the router.
6 Enable a port in the router for BACnet network.
l The protocol for the port, either IP or Ethernet, in the router must match the protocol
used by the service tool program.
l The BACnet network number assigned to the port must be unique on the BACnet
internetwork.
7 Enable the MS/TP port in the service tool router.
l Set the MS/TP network number in the router service tool to match the network
number that the devices on the building's network are using.
l Set the MS/TP MAC in the router that is unique on the MS/TP network.
l Set the baud rate to match the baud rate of the building's MS/TP network.
8 Start the service tool program. The BACnet devices on the internetwork will be
available for discovery. If it is a large internetwork, it may take a few minutes to
discover all devices.
Section 1: Introduction KMC Controls, Inc.