Start on Restart Select this check box and then click Save. The router will restart and
capture MS/TP traffic until the Max Time or Max Length is reached or the buffer is full. The
maximum amount of space to store captured data is 1 gigabyte. The router will capture
MS/TP traffic after every restart until Start on Restart is cleared.
Max Time Enter the length of time, in seconds, for a timed capture.
Max Length The amount of data, in bytes, to capture.
Last Start Time For information only. This is the time—as maintained by the clock in the
router—when the last capture started.
Last End Time For information only. This is the time—as maintained by the clock in the
router—when the last capture ended.
Capture Filled The percentage of available buffer space to store a capture. The maximum
amount of space to store captured data is 1 gigabyte.
Download Capture When this link is blue, captured data is ready to save to the computer on
which the browser is ruining. Data is saved in the file format .pcap (Packet CAPture). The
first capture is saved as Capture.pcap. Additional captures are saved with a number
added to the file name (Capture(1).pcap, Capture(2).pcap, etc.). Files are
saved in the downloads folder for the current Windows user.
Section 4: Diagnostics and status KMC Controls, Inc.
50 Revision J

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls BAC-5051E and is the answer not in the manual?

KMC Controls BAC-5051E Specifications

General IconGeneral
BrandKMC Controls
ModelBAC-5051E
CategoryNetwork Router
LanguageEnglish