BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs) Section 54 Application Guide L
FCU (Fan Coil Unit), 4-Pipe
Fan Control
The fan follows the base sequence for fan operation as listed in the Flex-
Stat (All Models) Common Features section above with the following
modications.
When the fan runs, whether in “Auto” or “On” mode, the fan speed is
determined by the Fixed Speed seing. If the Fixed Speed seing is set
to a particular speed (“1,” “2,” or “3”), then any time the fan is called for,
it will run at that speed. This allows fan speed to be set by a balancer. If
the Fixed Speed is set to “Auto” and the Fan Mode is set to “On,”then
the speed the fan runs is determined by the heating or cooling PI loops.
The fan is started at low speed upon call for heating or cooling and re-
mains there until the active heating or cooling PI loop reaches 60%. Once
above 60%, the fan is incrementally sped up based on the upper 40% of
the heating or cooling PI loop, whichever is active based on the number
of fan stages congured. The fan slows down in the reverse sequence.
This operation allows the FCU to aempt to maintain space temperature
setpoint using the valve at low fan speed. If space temp setpoint cannot
be maintained at low speed, increasing the fan speed will allow more
heat transfer to/from the coil. If the Fixed Speed is set to “Auto” and the
Fan Mode is set to “Auto,” then when the fan is called for, it runs on the
highest speed for which the unit is congured.
Valve Control
The method of controlling the heating and cooling valves is based on the
fan conguration:
The method of controlling the heating and cooling valves is
based on the fan conguration. If the fan mode for a particular
occupancy mode is set to constant or “On,” the valves func-
tion in a modulating fashion. Actual response may vary slightly
due to PI action of the control loops, but generally, the heating
valve will start to open as the space temperature drops below the
active heating setpoint and modulate to fully open when space
temperature reaches active heating setpoint minus deadband.
Likewise, the cooling valve will generally begin opening as the
space temperature rises above the active cooling setpoint and be
fully open by the time the space temp reaches the active cooling
setpoint plus deadband, modulating linearly in between.
With the fan mode set to “Auto,” the valves operate in a two-
position fashion. The heating valve will open 100% if the space
temperature falls below active heating setpoint minus deadband
and fully close when space temp rises above active heating set-
point. The cooling valve similarly opens 100% if the space temp
rises above the active cooling setpoint plus deadband and fully
closes if the space temp falls below the active cooling setpoint.
If at any time there is a fan failure alarm, the cooling and heating
valves are both forced closed.
Dehumidification
If the dehumidication sequence is enabled on models BAC-
10136C/11136C, the dehumidication mode is started and stopped as
described in the Common Features section above. Upon activation of the
dehumidication mode, the cooling valve is opened 100%. The heating
valve then reheats the space as called for in a modied heating sequence
to maintain the active cooling setpoint. Upon termination of the dehu-
midication mode, the valves return to their normal sequence.

Table of Contents

Other manuals for KMC Controls FlexStat

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls FlexStat and is the answer not in the manual?

KMC Controls FlexStat Specifications

General IconGeneral
BrandKMC Controls
ModelFlexStat
CategoryThermostat
LanguageEnglish

Related product manuals