4 Technical Description
16
4 Technical Description
4.1 Advantages of the LAMTEC measurement principle
• Direct (in situ) measurement of oxygen (O
2
) and oxidising exhaust gas
constituents (CO/H
2
) in crude gas up to 450°C
O
2
measuring range: 0 to 21 vol.% in conjunction with
CO
e
measuring range: 0 to 10,000 ppm LT 2/KS1-DK
• Uninfluenced by infiltrated air (CO
e
)
• No treatment of the gas required,
measurement directly in the damp flue gas
• Setting time to 60 % value (T90 ) <10 seconds with standard sampling
CO
e
< 2 seconds
• Measuring gas temperature up to 450°C
• Up to 1400°C possible with ejector pump
• Low heating power 20...25 watts
depending on the exhaust gas temperature
• Universal
• Easy to use
• Low-maintenance
4.2 Necessary components
• KS1-DK combination probe
• Flange gasket
• Internal/external reference air pump or compressed air connection
• LT 2/KS1-DK lambda transmitter in IP65 wall-mounted housing
incl. display and operating unit, or
• on IP00 mounting plate for installation in control cabinet, without display and
operating unit
(optional display and operating unit for installation in the control cabinet door,
cable length 1m, Type 657R0831T) or
Remote display software for Windows PCs Type 657R1101
}