4 Technical Description
30
4.7 Analogue output
Analogue output 1 - terminal 42 (-), 43 (+)
Output of O
2
value 0...10% Æ 4...20mA, or alternatively 0/2...10V
Analogue output 2 - terminal 44 (-), 45 (+)
Output of COe value 0...1000ppm Æ 4...20mA, or alternatively 0/2...10V
Optional modules 3 and 4
Parameters 530 / 540 / 550 / 560 Æ Setting the function:
• OFF /diagnosis
• O
2
measurement value
Configured measurement value 1...6
• Ri probe
O2 probe voltage (U-O2)
• COe
• U-COe
Parameters 531 / 541 / 551 / 561 Æ Setting the output value:
4...20mA / error 20mA
4...20mA / error 0mA
• 4...20mA
0...20mA / 0...10V
4…20mA / maintenance 0mA
Parameters 532 / 542 / 552 / 562 Æ Lower range limit
Parameters 533 / 543 / 553 / 563 Æ Upper range limit
Can be retrofitted at any time by means of plug-in cards on the LT 2/KS1-DK
processor board (max. 4)
Type 6 57 R 0050 non-floating
Type 6 57 R 0051 floating, maximum possible potential difference ± 20 V (only
possible with outputs 1 and 2)
Floating output card 657R0051
The jumpers only switch between the current and voltage outputs in terms of hardware.
The choice between 0 or 4...20mA is made using the parameters 531/541/551/561.