EasyManua.ls Logo

Lamtec LT 2 - Page 34

Lamtec LT 2
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Technical Description
32
4.8.1 Parameters of digital inputs
Idle state
Here you can set the idle state of the digital input. If the state differs from the one set
here, the actions predefined for the functions (A, B, C, D) are executed. If Diagnostic
mode is set here, the functions (A, B, C, D) can be initiated for the corresponding
digital input by means of the State parameter.
LOW (normal open contacts)
• HIGH (idle)
• Diagnostic mode
Functions A,B,C,D
The four functions are very similar in structure, but the assignment of the limit values
LV 1 - 4 or fuels to the individual functions
(A, B, C, D) is limited. Reset limit value 1 and Fuel 1 are only possible with function A;
Reset limit value 2 and Test gas 2 only with function B, etc.
The following actions are possible:
• None
Offset calibration Initiates offset calibration.
Fault reset Acknowledges present faults.
Warning reset Acknowledges present warnings.
Reset LV 1 (Function A) resets limit value 1, functions B, C and D
reset
the limit values 2, 3 and 4 respectively.
Therefore, the corresponding LVs must be set to
Acknowledge” in Reset mode
Fuel 1 (Function A only) selects fuel 1, functions B, C and D
select fuels 2, 3 and 4 respectively.
Probe 1 (Function A) selects probe 1, functions B, C and D
select probes 2, 3 and 4
No cal. Calibration disabled
PID controller On/Off If the PID controller option is enabled, here you can
switch off the PID controller.
Maintenance Switches the device to “Maintenance”
Deactivate Limit value x (also see section 4.13)
State
This parameter indicates the state of the digital input. The three possible states are
inactive (idle state) and active; the set functions (A, B, C, D) are initiated. The state of
the digital input can be set manually with this parameter, provided that the idle level
parameter is set to Diagnostic mode.
Parameters:
1175/1185/1195/1205/
1215/1225/1235/1245
Parameters:
1170/1180/1190/1200/
1210/1220/1230/1240
Parameters:
1171….1244

Table of Contents

Related product manuals