4 Technical Description
40
4.12.7 Digital outputs
Digital output 1 (standard):
Included as standard in LT 2/KS1-DK basic electronics via internal relay
(1 change-over contact) (terminals 1, 2 and 3, also see 10.3).
Switching capacity 230VAC / 2A and 42VDC / 3A
Digital outputs 2 to 7 (optional extra):
Via internal relay module Type 657 R 0857 (6 relays - 1 changeover switch)
Switching capacity 230VAC / 4A and 48VDC / 3A
Digital outputs can be configured as desired using the display and operating unit and
remote display software. Parameter groups 1030 to 1099.
Factory setting:
Relay output 1: Collective fault quiescent current method
Relay output 2: Warning and maintenance
Relay output 3: Measurement
Relay output 4: Limit value 1
Relay output 5: Limit value 2
Relay output 6: Limit value 3
Relay output 7: Limit value 4
Parameters of digital inputs
Idle state
Here, the idle state is set. This state is present when none of the functions triggers a
switching operation. The Diagnostic mode setting allows the idle state to be changed
via the State parameter (see below).
LOW (normal open contacts)
HIGH (idle state)
• Diagnostic mode
Parameters:
1030/1040/.../1090