8 System Operation
Fault
Code
No.
Restart according to Description
TRD EN676
451 1 1 Ignition position was left in ignition mode. Channel: 1
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
452 1 1 Ignition position was left in ignition mode. Channel: 2
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
453 1 1 Ignition position was left in ignition mode. Channel: 3
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
454 1 1 Ignition position was left in ignition mode. Channel: 4
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
455 1 1 Ignition position was left in ignition mode. Channel: 5
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
500 0 0 Internal comparison: relay out terminal 67 not picking up.
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol"> </Symbol> exchange the device or respective card.
501 0 0 Internal comparison: The relay output terminal 43 or 68 (ETAMATIC) does not
respond.
H See S500
502 0 0 Internal comparison: relay out terminal 16 or 65 (ETAMATIC) not picking up.
H See S500
503 0 0 Internal comparison: relay out terminal 11 or 66 (ETAMATIC) not picking up.
H See S500
504 0 0 Internal comparison: relay out terminal 45 not picking up.
H See S500
505 0 0 Internal comparison: relay out terminal 68 or 61 (ETAMATIC) not picking up.
H See S500
506 0 0 Internal comparison: relay out terminal 36 (ETAMATIC K202) not picking up.
H See S500
507 0 0 Internal comparison: relay out terminal 41 not picking up.
H See S500
508 0 0 Internal comparison: relay out terminal 76 not picking up.
H See S500
509 0 0 Internal comparison: Output K203 not picking up.
See S500
510 0 0 Internal comparison: Output K201 not picking up.
See S500