EasyManua.ls Logo

Lamtec VMS Series - Page 100

Lamtec VMS Series
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
99
8 System Operation
Fault
Code
No.
Restart according to Description
TRD EN676
451 1 1 Ignition position was left in ignition mode. Channel: 1
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
452 1 1 Ignition position was left in ignition mode. Channel: 2
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
453 1 1 Ignition position was left in ignition mode. Channel: 3
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
454 1 1 Ignition position was left in ignition mode. Channel: 4
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
455 1 1 Ignition position was left in ignition mode. Channel: 5
H/Ü In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
500 0 0 Internal comparison: relay out terminal 67 not picking up.
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol"> </Symbol> exchange the device or respective card.
501 0 0 Internal comparison: The relay output terminal 43 or 68 (ETAMATIC) does not
respond.
H See S500
502 0 0 Internal comparison: relay out terminal 16 or 65 (ETAMATIC) not picking up.
H See S500
503 0 0 Internal comparison: relay out terminal 11 or 66 (ETAMATIC) not picking up.
H See S500
504 0 0 Internal comparison: relay out terminal 45 not picking up.
H See S500
505 0 0 Internal comparison: relay out terminal 68 or 61 (ETAMATIC) not picking up.
H See S500
506 0 0 Internal comparison: relay out terminal 36 (ETAMATIC K202) not picking up.
H See S500
507 0 0 Internal comparison: relay out terminal 41 not picking up.
H See S500
508 0 0 Internal comparison: relay out terminal 76 not picking up.
H See S500
509 0 0 Internal comparison: Output K203 not picking up.
See S500
510 0 0 Internal comparison: Output K201 not picking up.
See S500

Table of Contents

Related product manuals