129
10 Appendix
10.9 R. P. M. Sensor
10.9.1 Direct Connection to R. P. M. Sensor
(old version delivered up to Sept. 03)
This option allows you to connect an inductive sensor of the company Turck as a speed feed-
back. On this configuration card 3 speed/ pulse ranges can be set at the factory.
Fig. 10-10 R.p.m. sensor 663P8001 delivered up to September 2003
Speed nominal range (164... 819 Digit)
I 300 ... 3000 pulses/min (Standard)
II 800 ... 4000 pulses/min (Standard)
III 1000 ... 8000 pulses/min
Range which is theoretically, technically possible (140-941 Digit)
I 200 ... 3500 pulses/min
II 680 ... 4600 pulses/min
III 740 ... 9310 pulses/min
Only 2 wire NAMUR.
If the set pulse range is exceeded the value remains at the upper end of the range (higher
pulse numbers are ignored).
Below the measuring range the signal goes to 0 (approx. 0 - 7 digit).
CAUTION!
Make sure that the selected measuring range is not exceeded, otherwise speed changes in
excess of this will no longer be detected.
Technical Data
NAMUR input: Technical Data NAMUR input: U
0
= 8,2 V; Ik = 8,2
mA, +/- 5 %
Make threshold: max. 2,1 mA (type 1,8 mA)
Break threshold: max. 1,2 mA (type 1,4 mA)
Linearity error: < 0,1 % v. E.
Temperature drift: < 75 ppm/K (type 60 ppm/K)