EasyManua.ls Logo

Lamtec VMS Series - O2 Trim; 6.6.1 Automatic Function Monitoring During Operation

Lamtec VMS Series
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
6 Commissioning
6.6 O
2
Trim
6.6.1 Automatic Function Monitoring During Operation
6.6.1.1 Adjusted The Integrated O2 Controller (Optional)
This section explains only the operating steps needed to input the O
2
curve. Further informa-
tion on O
2
controller is contained in the publication DLT 5002 Commissioning Supplement for
the Optional ’Integrated O
2
Controller’.
6.6.1.2 Test During Burner Start
The actual O
2
value is checked to ensure that during pre-purge it corresponds to the air value
(equal to or greater than 18 vol.% O
2
and less than 24 vol.% O
2
).
After ignition, the actual O
2
value must reach a value equal to or below 14% within 45 seconds.
Reaching the threshold value is monitored. If one of the two parameters is not met, O
2
trim is
deactivated. The control unit outputs the value “Base value without control”.
6.6.1.3 O
2
Monitoring Band
During burner operation, the actual O
2
value is continuously monitored for one maximum and
two minimum permissible values. These ranges are located around the O
2
setpoint as a func-
tion of firing rate. If the actual values stay outside these bands for a defined period, the control
system is deactivated and a “Fault” warning is output.
Thereafter, the control unit’s output (correction input) corresponds to “Base value without con-
trol” or “Base value with air deficiency”.

Table of Contents

Related product manuals