EasyManua.ls Logo

Lamtec VMS Series - 5.1.5 Start-up Sequence

Lamtec VMS Series
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
5 Firing Rate Controller (optional)
5.1.5 Start-up Sequence
The firing rate controller has a startup circuit, in order to slow down the burner's start firing rate.
The startup circuit is run during each new burner start. The internal firing rate is held at a value
P 792 adjustable by the user, for as long as the boiler is cold (actual value is below a user-
adjustable limit, P 791). If the controller’s actual value is equal to or larger than the parame-
terised startup maximum temperature, this startup circuit is cancelled.
In order to prevent a situation where an excessively large demand on system output, the boiler
temperature necessary to cancel the startup circuit is not reached, a startup timer is also trig-
gered in parallel (this timer can also be adjusted by the operator, P 793). Once the internal
firing rate reaches the parameterised startup firing rate, the output is increased linearly step-
wise up to the maximum firing rate. The slope of this linear increase is calculated from the pa-
rameterised startup time.
Fig. 5-2 Startup sequence
*(1) = P 792
*(2) = P 793

Table of Contents

Related product manuals