89
8 System Operation
Fault
Code
No.
Restart according to Description
TRD EN676
103 0 0 Internal fault: Error in misc. data
H/Ü The fault can occur during an internal self-test. A fault was discovered during the
reading of the redundant data in the EEPROM.
Reset the fault. In the process, switch the mains voltage off and on again if neces-
sary.
Check all fuses in the device.
Re-enter the curve.
Import the current data record into the device using the remote control software and
check this data record.
If the fault persists despite reset  the EEPROM is possibly defective:
Exchange the EEPROM.
Import the current data record into the device using the remote control software and
check this data record.
104 0 0 Internal Fault: D/A-Converter faulty
H Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If the fault message continues to persist exchange the device or respective card.