8 System Operation
Fault
Code
No.
Restart according to Description
TRD EN676
155 >88 3 the same as P 151, but channel: 5
H/Ü See S151
161 >88 3 Monitoring direction of ratation: channel 1
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
162 >88 3 Monitoring direction of ratation: channel 2
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
163 >88 3 Monitoring direction of ratation: channel 3
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
164 >88 3 Monitoring direction of ratation: channel 4
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
165 >88 3 Monitoring direction of ratation: channel 5
H/Ü The channel is not running or does not start on time. During operation, the channel
briefly changes direction.
Check the servo motor.
171 >88 3 Dead band over range too long: channel 1
H
172 >88 3 Dead band over range too long: channel 2
H
173 >88 3 Dead band over range too long: channel 3
H
174 >88 3 Dead band over range too long: channel 4
H
175 >88 3 Dead band over range too long: channel 5
H
181 >88 3 Dead band under range too long: channel1
H
182 >88 3 Dead band under range too long: channel 2
H
183 >88 3 Dead band under range too long: channel 3
H
184 >88 3 Dead band under range too long: channel 4
H
185 >88 3 Dead band under range too long: channel 5
H
191 1 1 1st monitoring band over range too long: channel 1
H/Ü