19
Display Description Press
Network Settings
Network Status
Panel Network
The Panel Network screen opens, with Network
Settings selected. Scroll down to Network Status.
Press Select
lect
Network Status
DONE
LM 0603981210
Net Status: Unhealthy
Net Device Count: <0>
The Network Status will display as “Unhealthy”
if it can’t find the BACnet network, or if devices
on network drop off and then reappear while the
LMCP is polling the network (indicating connection
problems). If devices show up consistently, or
if they disappear and do not show up again
(which would indicate the device was disabled or
disconnected), the status will display as “Healthy”.
The Net Device Count displays the number of
devices on the BACnet network.
Select DONE to return to the Panel Network
screen. Highlight DONE and press Select, or press
to return to the Panel Setup screen
lect DONE
Binding Buttons to Loads or Groups
You can bind any switch button to a specific load (relay) in the panel, or to a group. If you assign to loads, you can bind as many loads
as you want to a single button. If you assign to a group, you can only select one group.
Display Description Press
Location Settings
Date and Time
Network
Button Binding
Panel Programming
Status
Panel Setup
From Panel Setup, scroll to Button Binding.
Press Select.
Point at switch, and
press ‘Select’
Continue pointing to
the switch, then
press the button you
wish to assign
Point the LMCT-100 at the infrared sensor on the
switch that you want to bind and press Select. The
blue LED on each button on that switch will being
blinking. While the LMCT-100 is still pointed at the
switch, press the button that you want to bind.
lect
(004316987)
Type <Loads>
Load: <1>
Member: <Yes>
Button Assignment
SEND
The Button Assignment screen opens. For the
Type parameter, you choose between “Loads” and
“Group”.
If you select “Loads”, then you can select each
load individually using the Load parameter. With a
specific load selected, choose whether the button
will be bound to that load by setting the value of
the Member parameter. (“Yes” or “No”).
If you select “Group”, the Load parameter changes
to Group, and you select the group number to bind
the button to.
Highlight SEND and press Select. Once again,
point the LMCT-100 at the switch and press Select.
You return to the Panel Setup screen. At this point,
you can test the button turning it on and off. Repeat
the process to bind another button.