24
Display Description Press
Add or Remove loads
by using the
push button next to
each relay. When
finished, point to
the IR device
and select either
DONE CANCEL
Once you enter Smart wire mode, you can use the
Load buttons on the panel to assign the loads to
the group. See the Smartwire section on page 10
for details. Note that using this method, you can
program groups higher than #8 (up to group #99)
with Smartwire. Once finished, select DONE to
return to the Group Setup screen.
Se
lect DONE
Group 1 Custom Parms
NEXT DONE
Blink: <5 min>
Time Delay NH: <None>
Time Delay AH: <120 min>
NH > AH: <Do Nothing>
AH > NH: <Do Nothing>
If you select a value of “Custom” for Type on the
Group Setup screen, then you must select the
CUSTOM option on that screen, which opens
the Group x Custom Parms screen, which
contains the first five of the seven programmable
parameters. For definitions of these fields see
“Groups, Schedules, and Macros” on page 8.
Select NEXT to access the remaining two
parameters.
then choose
NEXTand
press Select
or
to move to each
parameter
or
to change the value
of the parameter
Group 1 Custom Parms
PRIOR DONE
AH: <Auto On/Off>
NH: <Auto On/Off>
Sensor Behavior
After setting the last two parameters, select DONE
to return to the Group Setup screen.
then choose
DONE and
press Select
or
to move to each
parameter
or
to change the value
of the parameter
Group: <1>
Type: <SensAutomatic>
Group Setup
LOADS CUSTOM
DONE DELETE SEND
Highlight SEND and press Select.
Once again, point the LMCT-100 at the infrared
sensor on the LMRD board and press Select. You
return to the Group Setup screen, where you can
program the next group.
When finished, highlight DONE and press Select to
return to the Panel Programming screen.
then choose
LOADS and
press Select
or
to move to each
parameter
or
to change the value
of the parameter
Occupancy Sensors
On this set of screens, you assign individual events that determine whether loads assigned to a group will turn on or off, based on input
from an occupancy sensor.
NOTE: If using multiple occupancy sensors, when programming with the LMCT-100, you should only assign ONE sensor input to a
group. Assigning more than one sensor to a group will lead to inconsistent response (but you can assign different sensors to
different groups). If you need to assign multiple sensors to a group, use the LMCS software to program the actions. The LMCS
software has additional capabilities for programming input from multiple sensors.
Display Description Press
603981210
Schedules
Holidays
Dark/Light
Groups
Occupancy Sensors
Panel Programming
From the Panel Programming screen, highlight
Occupancy Sensors and press Select.
then
Select
Point to the desired
Panel IR Sensor and
press ‘Select’
Point the LMCT-100 at the infrared sensor on
the LMRD board and press Select to open the
OccSensor Event screen.
Se
lect
Event Number: <1>
OccSensor Event
NEXT DONE DELETE SEND
Select the Event number in which to store the
occupancy sensor event. Then highlight NEXT and
press Select.
then choose
NEXT and
press Select
or
to change the value
of the parameter