APPENDIX A
BACnet Objects
NOTE: While there are 96 object instances available for many of the objects listed below, keep in mind that the LMCP panel supports
only 48 devices per network (A & B), and the panel itself is one of the devices in each network. Therefore, there is never a case
where you would use all 48 instances of an object in a single network.
Object Instance Object Alias Object Function
Device/Group Specific Control Objects
BO1–BO64 Loads 1–64, state Relay state, internally linked to the Analog Output objects by the trip
point parameter. Relay is ON above trip point and OFF below trip point.
Default trip point is 50% for LMRC-100 Series room controllers and 1%
for LMRC-200 and -300 Series room controllers.
AO1–AO64 Loads 1–64, level Dimming level, internally linked to the Binary Output objects by the trip
point parameter. Range = 0 to 100%.
AV1–AV96 Wattage Calculated based on the input voltage and measured current for room
controller 1 to 96. This only provides a valid reading if LMCS is used to
configure the “Baseline Wattage” values of all the panel’s relays. The
panel has no Current Transformers so this reading is also subject to
those loads operating correctly. If no full duty baseline power values
are configured, this value is calculated as AV501 * AV401 when any
one relay is active.
AV2-96 will only exist if any LMRCs or LMPLs or LMFCs are present
on the CAT5 networks A or B.
AV401–496 Input Voltage Per room controller, written by the user, default is 0.
AV402–496 will only exist if any LMRCs or LMPLs or LMFCs are
present on the CAT5 networks A or B.
AV501–596 Electrical current Read total current flowing through the room controller in amps, for
room controller 1 to 96.
AV502–596 will only exist if any LMRCs or LMPLs or LMFCs are
present on the CAT5 networks A or B.
AV101–AV196 Occupancy sensor 1–96, time delay For occupancy sensor 1 to 96, 0 to 30 minutes.
AV201–AV296 Occupancy sensor 1–96, PIR sensitivity Per PIR (passive infrared) sensor, 0 to 100% in percent, 10%
resolution.
AV301–AV396 Occupancy sensor 1–96, ultrasonic
sensitivity
Per ultrasonic sensor, 0 to 100% in percent, 10% resolution.
AI1–AI96 Exterior photocell Daylight level as read by LMIO-301 photocell input module 1 to 96.
AI4001–AI4096 Daylight sensor 1–96, light level Interior footcandle level as read by LMLS-400 daylight sensor 1 to 96.
AI5001–AI5096 Daylight sensor 1–96, light level Interior footcandle level as read by LMLS-500 daylight sensor 1 to 96.
AV4101–AV4196 Daylight sensor 1–96, ramp up rate For LMLS-400 daylight sensor 1 to 96, ramp up rate. Default is 20%
per second, writable in the range of 1% to 100 % per second.
AV4201–AV4296 Daylight sensor 1–96, day setpoint For LMLS-400 daylight sensor 1 to 96, day setpoint. Default is 50
footcandles, writable in the range of 1 to 255 footcandles.
AV4301–AV4396 Daylight sensor 1–96, night setpoint For LMLS-400 daylight sensor 1 to 96, night setpoint. Default is 10
footcandles, writable in the range of 2 to 255 footcandles.
AV4401–AV4496 Daylight sensor 1–96, off time delay For LMLS-400 daylight sensor 1 to 96, off time delay. Default is 10
minutes, writable in the range of 3 to 30 minutes.
AV4501–AV4596 Daylight sensor 1–96, on setpoint For LMLS-400 daylight sensor 1 to 96, on setpoint. Default is 7.5 foot-
candles, writable in the range of 1 to 3000 footcandles.
AV4601–AV4696 Daylight sensor 1–96, off setpoint For LMLS-400 daylight sensor 1 to 96, off setpoint. Default is 11.25
foot-candles, writable in the range of 1.5 to 6000 footcandles.
AV5101–AV5196 Daylight sensor 1–96, zone 1 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 1.
Writable in the range of 1 to 200 footcandles.
AV5201–AV5296 Daylight sensor 1–96, zone 2 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 2.
Writable in the range of 1 to 200 footcandles.
AV5301–AV5396 Daylight sensor 1–96, zone 3 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 2.
Writable in the range of 1 to 200 footcandles.
AV601–AV664 Loads 1–64, demand response cap
level
Maximum dimming level for load during a demand response (shed)
event. 100 = disabled.