LEGRAND Wattstopper LMCP48 - Group Status

LEGRAND Wattstopper LMCP48
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Display Description Press
Output Level: 100%
Load Type: NonDim
Grace Timer: None
Mode: Normal Hours
Blink: 5 min
Load 2 Pro perties 1
NEXT DONE
This screen indicates the current output of the load,
whether the load is a dimming or non-dimming
load. Mode indicates whether the load is currently
in Normal Hours or After Hours. Grace Timer
indicates whether the load is currently counting
down between Normal Hours and After Hours,
during the Blink period.
Highlight NEXT and press Select to see more
properties or select DONE to return to the Panel
Setup screen.
Se
lect
TDelay NH: None
TDelay AH: 120 min
NH–>AH: Turn Off
AH–>NH: Do Nothing
Load 2 Pro perties 2
NEXT PRIOR DONE
This screen displays parameters related to the
transitions between Normal Hours and After Hours.
Highlight NEXT and press Select to see more
properties or select DONE to return to the Panel
Setup screen.
Se
lect
Sensor Behavior
AH: Man On/Auto Off
NH: Auto On/Off
Load 2 Pro perties 3
PRIOR DONE
This screen displays the sensor behavior for this
load.
Highlight DONE and press Select to return to the
Status screen.
Se
lect DONE
Group Status
This set of screens displays the loads that are assigned to the group, along with their current on/off state. Additionally, you can view the
settings for the group. Finally, in cases where the setting of an individual load are different from the group settings, you can view the
differences. This can be extremely helpful when trying to diagnose a situation in which a load is not responding as expected. Keep in
mind that individual loads can be programmed with different values from the group but still be a member of the group.
Display Description Press
Group: <1>
Group Status
NEXT DONE
Select the Group number that you want to display,
highlight NEXT, and press Select.
then choose
NEXT and
press Select
or
to change the value
of the parameter
Point to the desired
Panel IR Sensor and
press ‘Select’
Point the LMCT-100 at the infrared sensor on the
LMRD board and press Select.
One of the following screens will display,
depending on the Status option you selected.