17. Electronic Configure To Order (ECTO) Control Parameters
Page 85
PRODIGYT M2 UNIT CONTROLLER
Control Parameter
No. Name
DescriptionUnits
Control Value
Min. Default Max.
Block 9 Optional A133 Board in GP Mode (DIP switch set to GP) Parameters (continued)
9.23
DO_Control_
Mode
0 0 127 Option
GP1 Digital Out Control Mode = X + 32*Y + 16*Z
Input source = X:
0− None.
1− Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.) On when OAT <= ECTO 9.24 and >= ECTO 9.25 seconds
have passed with compressor 1 off. Off when OAT > ECTO 9.24
+ 3 deg F (fixed deadband) or < ECTO 9.25 seconds have
passed with compressor 1 off.
2− On when occupied.
3− On when blower on,
4− On when heating demand.
5− On when cooling demand.
6− On when heating or cooling demand.
7− System RH (A55_P298_5 RH)
8− System IAQ. (A55_P298_3 IAQ)
9− System OAT (A55_P267_1/2 OAT)
10− On base on AI1. (A133_P194−6)
11− On based on AI2. (A133_P194−7)
12− On based on AI3. (A133_P194−8)
13− On based on AI4. (A133_P194−9)
14− On based on AO1. (A133_P194−11)
15− On based on AO2. (A133_P194−12)
Algorithm Y for input sources 7−15:
0− Hysteresis loop
On when input >= ECTO 9.24
Off when input < ECTO 9.24−ECTO 9.25
1− Window
On when input is in range; >= ECTO 9.24
and <= ECTO 9.24 + ECTO 9.25
(Fixed 3−count hysteresis loop on rising
and falling edges of window.)
2− Delayed−on.
On when input is >= ECTO 9.24
for >= ECTO 9.25 seconds.
Off when input is < ECTO 9.24 − 3.
(Fixed 3−count hysteresis loop on edge.)
3− Delayed−off.
On when input is >= ECTO 9.24.
Off when input is < ECTO 9.24 − 3
for >= ECTO 9.25 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
9.24−9.25 9.24
9.24 + 9.25
9.24
9.24
9.2
4
Delay
9.25
Graphs indicate output
not inverted. see figure
33.
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
9.24 DO_SP
0
0
16
0
132
−0.5
0
127
5.0
996
100
51
0
2.5
255
10.0
2000
100
−31
0.5
5.0
Counts
R:Volts
I:ppm
P: %
Y:DegF
M:"w.c.
N:"w.c.
Digital output control mode setpoint
9.25 DO_DB
2
0
0
2
1
64
0.01
0
13
.50
102
13
8
416
.05
.25
255
10.0
2000
100
162
8160
1.0
5.0
Counts
R:Volts
I:ppm
P: %
O:DegF
D:Sec.
L:"w.c.
N:"w.c.
Digital output control mode deadband or delay.

Table of Contents

Other manuals for Lennox PRODIGY M2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox PRODIGY M2 and is the answer not in the manual?

Lennox PRODIGY M2 Specifications

General IconGeneral
BrandLennox
ModelPRODIGY M2
CategoryController
LanguageEnglish

Related product manuals