Codes
Diagnostics codes
10
l
102
EDS82ZAFPC201 EN 4.0
C1526: Display of last configuration data
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1526 23049
d
=
5A09
h
g 0 [1] 65535 FIX32
1: byte 1
2: byte 2
3: byte 3
This code displays the current configuration frame selected in the PROFIBUS master via the
GSE file.
The configuration data indicate the following (see table below):
ƒ The type of the set parameter data channel
ƒ The length of the process data
ƒ The existence/non−existence of process data consistency
Consistent
channel
+ PZD ... Subcode Values Description
DRIVECOM−PAR(Cons) PZD(1W)
1
F3
hex
With consistent DRIVECOM parameter data channel and process data
2 70
hex
...
79
hex
With consistent DRIVECOM parameter data channel and process data
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PZD(1W Cons)
1 F3
hex
With consistent DRIVECOM parameter data channel and consistent
process data
2 F0
hex
...
F9
hex
With consistent DRIVECOM parameter data channel and consistent
process data
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
PKW(Cons) PZD(1W)
1 00
hex
With consistent PROFIdrive parameter data channel and process data
2 F3
hex
With consistent PROFIdrive parameter data channel and process data,
in this case byte 1 is 00
hex
3 70
hex
...
79
hex
With consistent PROFIdrive parameter data channel and process data
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PZD(1W Cons)
1 00
hex
With consistent PROFIdrive parameter data channel and consistent
process data
2 F3
hex
With consistent PROFIdrive parameter data channel and consistent
process data, in this case byte 1 is 00
hex
3 F0
hex
...
F9
hex
With consistent PROFIdrive parameter data channel and consistent
process data
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
PZD(1W)
1
70
hex
...
79
hex
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PZD(1W Cons) F0
hex
...
F9
hex
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
I Tip!
Observe the descriptions concerning
ƒ the user data length ( 31)
ƒ the meaning of consistency ( 110)

Table of Contents