Technical data
Communication time
4
l
16
EDS82ZAFPC201 EN 4.0
Terminal
X3.2/
Designation Function / level
+ PES Additional HF shield termination
A T/R(A) RS485 data line A
B T/R(B) RS485 data cable B
CN CNTR For function see PROFIBUS standard *)
l Level during data transmission: CNTR = HIGH
(+5 V DC, reference:GND3)
VP For function see PROFIBUS standard *)
l U = +5 V DC (reference:GND3)
l I
max
= 10 mA
40 GND3 Reference potential for PROFIBUS network *)
7 GND1 Reference potential for X3.1/20 and X3.2/20
39 GND2 Reference potential of the
l digital inputs at X3.1/E1 and X3.1/E2
l controller inhibit (CINH) at X3.2/28
28 CINH Controller inhibit
l Start = HIGH (+12 ... +30 V DC)
l Stop = LOW (0 ... +3 V DC)
(reference: GND2)
20 DC voltage source for internal supply of controller inhibit (CINH)
l +20 V DC (reference: GND1)
l I
max
= 20 mA
59 External DC voltage supply for the function module
l +24VDC±10% (reference: GND1)
l Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes via
terminal 59 must be max. 3A.
*) E.g. for repeater connection
4.5 Communication time
The communication time is the time between the start of a request and the arrival of the
corresponding response.
The communication times depend on ...
ƒ the processing time in the controller
ƒ the transmission delay time
– the baud rate
– the telegram length
Processing time 8200vector / 8200motec / starttec
There are no interdependencies between parameter data and process data.
ƒ Parameter data: approx. 30 ms + 20 ms tolerance
ƒ Process data: approx. 3 ms + 2 ms tolerance