Installation
Electrical installation
Terminal assignment
5
l
24
EDS82ZAFPC201 EN 4.0
External voltage supply via two voltage sources:
ƒ X3.1/E1 and X3.1/E2 (digital inputs) and
X3.2/28 (controller inhibit (CINH))
ƒ X3.2/59 (function module)
E82ZAFP002 (V201)
Minimum wiring required for operation
5.2.4 Terminal assignment
Terminal
X3.1/
Designation Function / level
E1
Digital inputs *)
Adapt the individual setting via C0007 or C0410.
l Input resistance: 3.3 kW
l 0 = LOW (0 ... +3 V DC) PLC level, HTL
l 1 = HIGH (+12 ... +30 V DC) PLC level, HTL
(reference: GND2)
E2
20 DC voltage source for the internal supply of the digital inputs E1 and E2
l +20 V DC (reference: GND1)
l I
max
= 20 mA
39 GND2 Reference potential of the
l digital inputs at X3.1/E1 and X3.1/E2
l controller inhibit (CINH) at X3.2/28
59 External DC voltage supply for the function module
l +24VDC±10% (reference: GND1)
l Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes via
terminal 59 must be max. 3A.
7 GND1 Reference potential for X3.1/20 and X3.2/20
*) Alternatively frequency input 0 ... 10 kHz (one−track) or 0...1kHz (two−track) configuration via C0425