Codes
Monitoring codes
10
l
96
EDS82ZAFPC201 EN 4.0
C1514: Monitoring reaction in case of PZD communication fault
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1514 23061
d
=
5A15
h
0
0 [1] 3
FIX32
0: no action
1: TRIP (fault)
2: controller inhibit (CINH)
3: quick stop (QSP)
If the master does not send a message within the response monitoring time (configurable
in C1513), the action set in this code is executed.
) Note!
A change in the monitoring reaction becomes effective immediately.
C1572: Response time after exiting "Data_Exchange"
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1572 23003
d
=
59DB
h
65535 0 [1 ms] 65535 U16
If the "Data_Exchange" state is exited, the reaction parameterised in code C1514 is carried
out after the time set here has expired.
) Note!
ƒ The set response time must be shorter than the response monitoring time in
C1513.
ƒ A change in the monitoring function becomes effective immediately.
The setting C1514 = 65535 deactivates the monitoring function.