13 Parameter reference
13.3 Parameters of the communication module for slot MXI2
113
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14871
C14872
C14873
Parameter | Name:
C14871 | CIP Connections Type
Data type: UNSIGNED_16
Index: 9704 = 0x25E8
Display of the current CIP connection types
"Listen Only" connections are not displayed.
Selection list (read only)
0 Nonexistent
1 Exclusive Owner
2 Input Only
3 Listen Only
4 Explicit Connection
Subcodes Info
C14871/1 Type of CIP connection 1
... ...
C14871/8 Type of CIP connection 8
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14872 | CIP Connection Triggers
Data type: UNSIGNED_16
Index: 9703 = 0x25E7
Display of the current CIP connection class
Selection list (read only)
0 Nonexistent
1 Class 1, Cyclic, Client
163 Class 3, App. Obj., Server
Subcodes Info
C14872/1 Trigger of CIP connection 1
... ...
C14872/8 Trigger of CIP connection 8
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14873 | CIP Connections RPI
Data type: UNSIGNED_32
Index: 9702 = 0x25E6
Indication of the current RPI times (Requested Package Interval) of the CIP connections
Display range (min. value | unit | max. value)
0 ms 4294967295
Subcodes Info
C14873/1 RPI of CIP connection 1
... ...
C14873/8 RPI of CIP connection 8
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT