Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17 66
8 I/O data transfer (implicit messages)
8.4 I/O configuration with »RSLogix 5000« version 20 or higher
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Go to the "Module Definition" dialog window and make the connection settings.
The terms "input" and "output" refer to the point of view of the scanner:
Assembly input objects (input) are sent from the adapter to the scanner.
Assembly output objects (output) are sent from the scanner to the adapter.
9. Complete the settings with OK.
Settings Value / description
Name Name (type) of the connection
"Exclusive owner": The scanner controls the adapter outputs.
"Listen only": If a connection has been established, the scanner only
receives the input data.
"Input only": The scanner does not transmit any output data to the
adapter, but only receives the input data.
Number of I/O data words A maximum of 32 data words (max. 64 bytes) for each direction
Selection of the data type The number of input data must correspond to the length of the mapped
ports in the transmit PDO (PDO_TX0), otherwise the adapter will reject
the connection with the error message "Invalid Target to Originator Size"
(0x0128).
The number of output data must correspond to the length of the mapped
ports in the receive PDO (PDO_RX0), otherwise the adapter will reject the
connection with the error message "Invalid Originator to Target Size"
(0x0127).